Monitor treatment efficacy with bioboxes located at critical points in the system.
Do not store in low-density polyethylene, polypropylene, or copper, zinc, aluminum, and their alloys.
Store on impermeable surfaces within retention basin.
Avoid any discharge onto the ground. Protect sewers from possible discharges.
Monitor the presence of MEXEL 432 with colorimetric tests of grab samples, or with an electrode (Corroprobe®) measuring free corrosion potential as electrical potential.
Required dosage varies with the solids content of the water and with the temperature. When seasonal water turbidity is high, dosage may need to be increased; dosage may be reduced when water is cleaner. Colder water may require decreased dosage due to slower biodegradation rates. Biodegradation increases with increasing temperature and oxygen availability, and can be accelerated by agitation and by aeration.